Office Pro 60
- Operates on 220v power.
- Provides 60,000 Btu/hr of cool air... maximum spot cooling to just the room that needs it.
- No costly installation necessary ... simply roll it in, plug it in, turn it on.
- Condensation pump included ... pumps water to remote drain for uninterrupted operation.
- 24/7 programmable operating modes
Computer Cooling
Providing up to 60,000 Btu/hr of computer cooling capacity (more than twice the cooling power of the Office Pro 24), the Office Pro 60 portable air conditioner is specifically designed for cooling large office spaces and computer rooms that house heat-generating electronics. As an ideal server room air conditioner, it prevents computer networks, communications, and office equipment from shutting down when temperatures rise.
Avoid crippling daily operations by bringing portable A/C to just the area or room that needs it. Protect critical data from being lost with an Office Pro 60. This powerful computer room air conditioner saves you money while protecting your company's investment in equipment, employees and customers. Self-contained and portable, the Office Pro 60 requires no costly installation - simply roll it in, plug it in and turn it on.
** Exhaust duct required in most cases.
Accessories
| No. | Part Name | Office Pro 60 - Part Description | Part Number |
|---|---|---|---|
| 1. | Nozzle Adapter Kit | Three-piece metal frame converts airflow from louvers to nozzles or cold air ducts. Includes mounting screws. (Nozzles and ducts sold separately.) |
LAY45770-0070 |
| 1A. | Duct Adapter Kit | Same as above, but for use with cold air flexible ducts. Includes flange. (Cold air flexible ducts sold separately.) |
LAY45770-0080 |
| 2. | Nozzle Kit | 6" diameter white plastic nozzle that extends up to 2' in length. Includes flange, mounting screws and trim ring. (Purchase in sets of two.) |
484209-0050 |
| 3. | Cold Air Flange Kit | 6" diameter white metal flange with wire clamp and mounting screws.Use with cold air ducts. |
481170-0250 |
| 4. | Cold Air Extension Duct | 6" adjustable diameter, white plastic duct that extends from 6-1/2' to 10' in length. |
481744-0030 |
| 4A. | Cold Air Flexible Duct | 8" diameter wire-reinforced, accordion-style duct in 25' lengths. |
LAY45810-0030 |
| 4B. | Cold Air Self-Supported Duct | 8"adjustable diameter, white plastic duct that extends from 6-1/2' to 10' in length. |
LAY45810-0080 |
| 5. | Trim Ring | 6" diameter black plastic ring mounts as end caps for extension duct. |
481851-0210 |
| 7. | Ceiling Tile Kit | 24" x 24" sheet metal tile with 16" hole for warm air flexible duct kit |
GX484410-8940 |
| 8. | Condenser Air Plenum | White plastic plenum for return air to condenser. Hinged for filter cleaning. |
LAY84270-0060 |
| 9. | Condensate Pump Kit | Included with this model. |
Included |
| 10. | Condensate Tank | Drain tank storage for condensation. Requires condensate float, sold separately. (For OP60 only) |
484730-0010 |
| 10A. | Condensate Float (not shown) | Controls water level in condensate tanks. (For OP60 only) |
484460-0010 |
| 11. | Evaporator Air Plenum | White plastic plenum for return air to evaporator. |
LAY84270-0070 |
| 12. | Warm Air Flexible Duct Kit | 16" diameter wire-reinforced, accordion-style duct in 25' length for condenser exhaust or evaporator intake. Includes clamp. |
LAY45820-0010 |
Specifications
Electronic Features |
Control Panel Thermostat Control |
Programmable Electronic |
Cooling Capacity |
Rating Conditions: 95F at 60% RH |
60,000 Btu/h |
Electrical Characteristics |
Voltage Requirement Total Power Consumption Current Consumption Recommended Fuse Size NEMA Plug Configuration Min. Max. Voltage |
1 Phase, 208/230V 6.6 kW 29 amps 50 amps 6 - 50 198 - 250 |
Fans |
Motor Output |
0.5/0.33 kW Evap. 1.2/0.93 kW Cond. |
Evaporator |
Fan Type Max Air Flow high/low Max External Static Pressure |
Centrifugal 1940/1770 CFM 0.9 IWG |
Condenser |
Fan Type Max Air Flow high/low Max External Static Pressure |
Centrifugal 2830/2650 CFM 0.85 IWG |
Compressor |
Type Output |
Hermetic Rotary 3.9 kW |
Refrigerant |
R-410A |
3.97 lb |
Dimensions |
W x D x H |
30 x 52 x 64 in |
Net Weight/Shipping Weight |
623/753 lb |
|
Power Cord |
Gauge Length |
6 AWG (3 - core) 6 ft |
Condensate Tank Capacity |
Auto Pump Included |
|
Operating Conditions |
Min. Max. (@ 50% RH) |
65° - 105°F |
Max. Duct Length |
Per Cold Duct Hose Hot Duct Hose |
40 ft 100 ft |
Max. Sound Level |
With Condenser - Duct high/low Without Condenser - Duct high/low |
69/67 dB(A) 71/69 dB(A) |
* Specification information shown with 230V.